Output Signal 4–20mA
Output Type
Single pole, double throw relay adjustable from 10 to1200 amps in ten amp increments. 4–20 mA signalproportional to 0-1200 amps. Analog signal capped at6mA when trip point <150 amps, 8mA if trip point <300amps, 23mA if the trip point is 310 or higher.
Output Limit 4–20mA: 23mA (If trip point is <150 A,max. signal is 6mA, if <300A, max signalis 8mA)
Transducer Accuracy +/-1%
Repeatability 1.0% FS
Response Time
Relay Output:: 200ms to 90% of stepchange
Transducer: 600ms to 90% step change
Frequency Range AC 10–100 Hertz
Power Supply 120 VAC , isolated from output
Power Consumption 5VALoading 4–20mA: 650 ohm maximum
Isolation Voltage Tested to 5KVLinearity 1.00% FS
Current Ranges: from 0–1200A
Sensing Aperture DL Case: 1.875” (46mm) diameter
Case UL94 V0 Flammability Rated
Environmental -4 to 122oF (-20 to 50oC), 0–95% RH,non-condensing
Listings UL 508 Industrial Control Equipment Standards(Pending, USA & Canada)Designed to meet CE
|