Ideally suited for outdoor testing of grounded and ungrounded systems, especially in areas where an LED lamp is not easily visible. The large, 3.5-in. (89-mm) analog scale is calibrated to indicate the presence of nominal system voltages; the tester cannot be used to determine an exact voltage measurement. may be used on grounded and ungrounded ac systems to check high-voltage fuses, test for correct phase connections and test for the absence of high voltage on de-energized lines or apparatus.
Provides continuous monitoring with no on/off switch. They respond to minimum phase-to-ground voltages as outlined by ANSI C84.1 standards, with conformance to IEC guidelines for capacitive high-voltage test instruments. Prior to testing, a self-test may be activated on the electronic detectors at the push of a button. The test simulates application of external voltage to the probe electrode, which verifies the operation of the buzzer and lights a red LED. When the TEST button is released, a green LED indicates the detector is operative and ready for use. If voltages within the detector’s operating range are present during testing, the green LED extinguishes, the red LED flashes and the audio tone sounds until the detector is removed from the voltage source.
• Used to check high voltage fuses, test for correct phase connections, and check for absence of high voltage on de-energized lines or other electrical apparatus
• Ideally suited for outdoor testing of grounded and ungrounded systems and in any other area where neon indicators are not easily seen
All ratings per ANSI C84.1, with conformance to IEC guidelines for capacitive high-voltage test instruments. All are self-powered.
The kilivolt indicator markers are: 0, 1.4kv, 2.4kv, 4.2kv and 6.9kv